smartLink HW-PN - Manage PROFINET and PROFIBUS devices
smartLink HW-PN provides controller independent access to PROFINET networks. It can be used with standard industry tools for asset management, device configuration and monitoring. smartLink HW-PN provides transparent access to connected PROFINET, HART and PROFIBUS devices.
Overview
Plant Asset Management and Parameterization using Standard Industry Tools
Independent from PROFINET engineering tools
Centralized and time-saving asset management of PROFINET networks with PROFINET, HART and PROFIBUS field devices directly from the control room
Access from Plant Asset Management applications for field devices based on the FDI standard
Network Monitoring of PROFINET networks
Prevent unplanned downtimes of production lines with PROFINET networks
Get messages indicating problems in the network or with installed devices
Full overview of the PROFINET network and all installed devices
Access the data with the IT friendly MQTT protocol
Ethernet Access Point to PROFINET networks
Provides 2nd channel to access the field devices
Acts as a PROFINET supervisor
Is part of one PROFINET network
Integrated 2-port switch for use in line network topologies
Key Component for Transition to State-of-the-Art Technology
Re-use of existing PROFINET networks without requiring modification
Access to acyclic data via FDI communication server (OPC UA) or HART-IP
Access to network monitoring data via MQTT
Asset Management and Parameterisation of PROFINET Devices
Plant Asset Management and Parameterisation
Secure, standardised access to devices
Parallel to and independent of the controller
Compatible with established standard applications
Proven and tested with Emerson AMS Device Manager and ABB FIM
Implements the standard FDI communication server interface based on OPC UA

Asset Management and Parameterisation of HART Devices
Plant Asset Management and Parameterization
Secure, standardized access to devices
Parallel to and independent of the controller
Compatible with established standard applications
Proven and tested with Emerson AMS Device Manager
Implements the standard HART-IP server interface
Transparent HART communication
HART commands sent to the HART-IP server are forwarded to the HART devices
No limitation on the supported HART commands
Uses the open HART-IP protocol
Access HART devices without additional Hardware
Use the existing infrastructure to access the HART devices
No additional cost for HART multiplexer hardware
No installation and maintenance of additional Hardware

Asset Management and Parameterization of PROFIBUS Devices
Plant Asset Management and Parameterisation
Secure, standardized access to devices
Parallel to and independent of the controller
Inexpensive and low-risk Integration
Connection of PROFIBUS devices without additional hardware
Use of existing infrastructure using the PROFINET/PROFIBUS proxy standard for connecting to the PROFIBUS devices
Compatible with established standard applications
Proven and tested with Emerson AMS Device Manager
Implements the standard FDI communication server interface based on OPC UA

Network Monitoring in PROFINET Networks
Complete inventory of the entire network
Complete network topology data
I&M data from all connected devices
Automated live queries without configuration
Secure provision of data using MQTT
Secure IT friendly transmission method
Information model based on OPC UA Companion Specifications for PROFINET
Health monitoring of all connected devices
Diagnostic messages and NE107 status of all devices
Statistics parameters of all network devices
Integrated with Softing plantPerfect Monitor application
Use the plantPerfect Monitor application to monitor the network with all its devices

Hardware
Status LEDs (Gateway)
PWR, RUN, ERR, BUS
Interfaces
Ethernet
1 x IEEE802.3 10BASE-T/100BASE-TX/1000BASE-T, Connector: RJ45
PROFINET
2 x IEEE802.3 10BASE-T/100BASE-TX, Connector: RJ45; Embedded PROFINET 2-port switch for line topology
Protocol: PROFINET RT / IRT, Support of PROFINET redundancy protocols
Supported
Communication Protocols
PROFINET, PROFIBUS
FDI communication server (OPC UA), MQTT
PROFINET/PROFIBUS Proxies
Softing: pnGate DP, pnGate PA, aplSwitch Field PA
Pepperl + Fuchs: Ethernet-APL Rail Field Switch (Firmware >= V1.3.1)
R.Stahl: Ethernet-APL Field Switch
HART Controller and Remote IOs
Siemens:ET 200iSP: PROFINET IM152-1PN: 6ES7152-1BA00-0AB0 (redundant)
ET 200SP: PROFINET IM155-6PN (High Feature): 6ES7155-6AU01-0CN0,PROFINET IM 155-6 PN/3: 6ES7155-6AU30-0CN0 (redundant),PROFINET IM 155-6 PN R1: 6ES7155-6AU00-0HM0 (redundant)
ET 200SP HA: PROFINET IM155-6PN, 6DL1155-6AU00-0PM0 (redundant)
ET 200M: PROFINET IM153-4 PN (High Feature): 6ES7153-4BA00-0XB0
ET 200MP:IM 155-5 MF (High Feature): 6ES7155-5MU00-0CN0
CFU HART: 6ES7655-5PX41-1XX0
Supported HART IO Modules
Siemens:ET 200iSP: 6ES7134-7TD00-0AB0, 6ES7134-7TD50-0AB0, 6ES7135-7TD00-0AB0, 6ES7138-7FA00-0AB0
ET 200SP: 6ES7134-6TD00-0CA1, 6ES7135-6TD00-0CA1
ET 200SP HA: 6DL1133-6EW00-0PH1, 6DL1133-6EW00-0EH1, 6DL1134-6TH00-0PH1, 6DL1134-6UD00-0PK0, 6DL1134-6TB00-0HX1, 6DL1135-6TF00-0PH1 6DL1135-6UD00-0PK0, 6DL1135-6TB00-0HX1, 6DL1135-6TF00-0EH1, 6DL1136-6AA00-0PH1,with optional module redundancy
ET 200MP:6ES7531-7TF00-0AB0, 6ES7532-8TF00-0AB0
ET 200M: 6ES7331-7TF01-0AB0, 6ES7332-8TF01-0AB0, 6ES7331-7TB10-0AB0, 6ES7332-5TB10-0AB0, 6ES7336-4GE00-0AB0
Asset Management Applications
Emerson AMS Device Manager >=V15
ABB Field Information Manager (FIM) >= V3.3
Physical Properties
Dimensions (H x W x D)
120 mm x 28 mm x 110 mm
Power Supply
18 VDC ... 32 VDC; SELV/PELV power supply mandatory
Typical input current: 200 mA, maximum input current: 1 A (allowing for in-rush current at switch-on)
Typical Power
5 W
Operating Temperature
-40 °C ... +65 °C (see detailed mounting description in user manual)
Relative Humidity
10 % ... 95 %, non-condensing
Cooling
Convection, no fan
Mounting
DIN rail 35 mm
Protection Class
IP20