top of page
FG-200

FG-200

SKU: GLA-EK-024102

Modbus TCP/FF HSE to FF H1 Gateway

Direct FF H1 segment integration - Modbus TCP control systems or FF HSE asset management applications

With Softing’s FG-200, it is possible to integrate up to four FOUNDATION™ Fieldbus (FF) H1 links into control systems supporting Modbus TCP or into FF asset management applications. The FG-200 provides redundancy and is suitable for use in hazardous areas. This device features fast access to process data, while making use of FF advantages like reduced cabling, central field device parameterization, comprehensive diagnostics, or intrinsically safe device segments.


Overview

Integration of FF-H1 devices into Modbus TCP control systems

  • Parallel support of up to 4 FF-H1 channels, each for max. 16 field devices

  • Fast access to process data

  • Suitable for use in hazardous areas

  • FF Configuration Tool for easy commissioning

Access to FF H1 devices from plant asset management applications

  • Visitor mode for avoiding interference with network behavior

  • FF HSE interface for EDD based applications like Emerson’s AMS Device Manager (< V14.5 or >= V15)

  • DTM for FDT applications like PACTware, Yokogawa FieldMate, Honeywell FDM, E+H FieldCare

High availability

  • Redundancy link enabling device redundancy (D-3 according to FF-593)

  • Automatic mirroring of configuration data

  • Very fast redundancy switchover

The FG-200 is the successor product of FG-110.

  • Hardware

    Processor

    Altera Cyclone V SoC with dual-core ARM Cortex-A9

     

    Status LEDs (Gateway)

    PWR (power supply), RUN (operation), ERR (error), RDL (redundancy link)

     

    Status LEDs (Fieldbus)

    FF H1 activity per link

    Interfaces and Connectors

    Ethernet

    2 * IEEE 802.3 100BASE-TX / 10BASE-T (only ETH1 supported)


    Connectors: RJ45

     

    Fundation Fieldbus H1

    4 FF H1 links, compliant to type 114 of FF physical layer profile


    (each link capable to operate independently as Link Master and/or Time Master)


    Transfer rate: 31.25 Kbit/s


    Fieldbus voltage range: 9 VDC ... 32 VDC, preferred voltage: 24 VDC


    Current consumption: 10 mA / link


    Connectors: 3-position screw connection, galvanically isolated

    Physical Properties

    Dimensions (H x W x D)

    100 mm x 35 mm x 105 mm

     

    Weight

    Approx. 250 g

     

    Power Supply

    18 VDC ... 32 VDC; SELV/PELV power supply mandatory; Typical input current: 200 mA, maximum input current: 1 A (allowing for in-rush current at switch-on)


    No power supply to FF H1 links through FG-200 HSE/FF Modbus

     

    Operating / Storage Temperature

    -40 °C .. +70 °C / -40 °C .. +85 °C (see detailed mounting description in user manual)

     

    Relative Humidity

    10 % ... 95 %, non-condensing

     

    Cooling

    Convection, no fan

     

    Coating

    Conformal coating based on ANSI / ISA-S71.04 G3

     

    Mounting

    DIN rail 35 mm

     

    Protection Class

    IP20

    Software

    Protocols

    FOUNDATION Fieldbus H1, FOUNDATION Fieldbus HSE, Modbus TCP

     

    Redundancy

    Device redundancy compliant to type D-3 according to specification FF-593

    Conformity / Certifications

    CE

    EN61000-6-2, EN61000-6-4, EN55022 Limit Class A, EN55011

     

    Electromagnetic Compatibility (EMC)

    FCC CRF47, Part 15 Section 15.107 and 15.109 (Class A), VCCI Class A Information Technology Equipment 2002

     

    Vibration / Shock

    DIN EN 60068-2-6 Vibration / DIN EN 60068-2-27 Schock

     

    Hazardous Location Certifications

    cULus: Class 1, Division 2, Groups A, B, C, D


    IECEx: Ex ec [ic] IIC T4 Gc


    ATEX: Ex II 3G ec [ic] IIC T4 Gc


    CCC :  Ex ec [ic]  IIC T4 Gc 


£3,554.00Price
Quantity

For further information, pricing and lead times contact us.